Description
• High resolution graphic LCD display for viewing actual or programmed values
• Easy and intuitive menu navigation via 5-way joystick or USB PC link
• Universal Input accepts all common process variables in just one device
• Universal auxiliary supply voltage (DC and AC)
• Din rail mounting bases ensure quick and safe installation
• Transmitter can be plugged in and exchanged while system is live and without rewiring
Compare the TELIS range with other leading brands and discover their higher specification and special features; In particular their ease of configuration and separate wiring bases for quick and safe installation / commissioning.
The TELIS universal transmitter’s measure, isolate, convert, transmit and control process analogue signals, temperature and electrical values. They are used across a wide range of applications in Environmental Control, Power Generation, Pharmaceutical, Petrochemical, Railway and Machinery Industries.
For the best and most versatile Signal Isolators & Conditioners specify and fit a TELIS universal transmitter.
| Input - Single Universal (or 2 current inputs with calculation function) | ||
| Current DC | Standard Ranges | 1mA, 10mA, 20mA, 4/20mA, ±1mA, ±10mA, ±20mA. |
| Adjustable Range | From -22mA to +22mA | |
| Voltage DC | Standard Ranges | 100mV, 1V, 5V; 1/5V, 10V, 2/10V, 50V, 100V, 200V, ±100mV, ±1V, ±5V, ±10V, ±50V, ±100V, ±200V. |
| Adjustable Range | From -110mV to +110mV, from -2V to 11V from -200V to 220V. | |
| RTD | PT100, PT1000 2 or 3 wires (4 wires an option) Ni100, Ni1000 2 or 3 wire. | |
| Thermocouple | J, K, R, S, T, E, B, N,W3, W5, NiMo | |
| Potentiometer | From 100Ω to 100KΩ (other values on demand) | |
| Resistor 2 wire | 0-200Ω, 0-1KΩ, 0-10KΩ, (other values on demand) | |
| Sensor supply | Sensor 2 or 3 wires - Sensor supply 24V, 29mA max. | |
| Outputs - Single | ||
| 2 Analogue Isolated | Current or | 20mA, 4/20mA - From 0 to 20mA |
| Voltage | 10V, ±10V - From 0 to 10V | |
| Digital | RS485 | Modbus Jbus on screw terminals |
| via USB socket on front face | ||
| Relays | 1 Relay 1C/O | |
| Specification | ||
| Display | LCD graphic blue backlit display | |
| For inputs | displays actual or programmed value | |
| For outputs | displays actual, percentage or programmed value and alarm status | |
| Auxiliary Voltage Supply | 20-370V DC and 80-256V AC (20-60V AC optional) | |
| Configuration / programming | Either via 5-way joystick on front face or | |
| Or connecting via the USB socket to a PC running easy to use software | ||
| Basic Input selection made using accessible DIL switch | ||
| Precision class | < 0.10 | |
| Analogue input digital conversion | 24 bits | |
| Digital output / analogue conversion | 16 bits | |
| Response time | < 250 mS | |
| Thermal drift | < 50 ppm | |
| Current output residual ripple | < 20 μA | |
| Isolation | 3750V AC | |
| Consumption (max) | < 4VA | |
| Temperature range | Operating | -10° to +60°C |
| Storage | -25° to +80°C | |
| Case | Size - transmitter only | 22.5 wide x 81 high x 98mm deep |
| Size with terminal base | 22.5 wide x 121 high x 134mm deep | |
| Protection | to IP20 | |
| Additional functions | Input scale factor | Providing a magnifying effect on input 1 in manual or automatic calibration |
| Output scale factor | Providing a magnifying effect on outputs and display | |
| Min./ Max. memory | ||
| Safety sensor | Shows break on display, on output (against threshold value) & on relay output | |
| Linearization | 100 point linearization | |
| Square root | Output is computed as square root of input | |
| Thresholds | ||
| Other functions | Cut-off; resolution; comma, filtering; contrast setting; programming mode; display backlight off; joystick lock. | |